| 2006-06-22 00:00:00 | *** DENIED *** |
| | 1) BUILDING PLANS SHOW TOTAL SQ. FEET |
| | UNDER AIR AS 2834, THE ENERGY |
| | CALCULATIONS SHOW TOTAL SQ. FEET UNDER |
| | AIR AS 3056, THE TWO MUST COINCIDE |
| | PLEASE CORRECT. |
| | |
| | 2) HAVE NEW ENERGY CAL'S. SIGNED BY |
| | OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2 |
| | |
| | 3) SUBMIT A COMPLETE SET OFMANUAL J |
| | CALCULATIONS, PER 2004 FBC |
| | 13-607.1.ABC.1 . |
| | |
| | 4) SHOW A/C SYSTEM'S SENSIBLE BTU'S AND |
| | TOTAL BTU'S ON MECH. SCHEDULE. |
| | |
| | 5) MECH. PLANS ARE SHOWING TWO RETURN |
| | AIR GRILLS FOR EXISTING BEDROOM #2, |
| | PLEASE CORRECT AND SHOW CORRECT SIZE OF |
| | RETURN AIR DUCT. |
| | |
| | 6) RETURN ARI TRANSFER DUCT TO EXISTING |
| | BEDROOM #3 IS TO SMALL, SEE NOTE #7. |
| | |
| | 7) BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | |