Plan Review Notes
Plan Review Notes For Permit 05020987
Permit Number 05020987
Review Stop M
Sequence Number 3
Notes
Date Text
2006-06-22 00:00:00*** DENIED ***
 1) BUILDING PLANS SHOW TOTAL SQ. FEET
 UNDER AIR AS 2834, THE ENERGY
 CALCULATIONS SHOW TOTAL SQ. FEET UNDER
 AIR AS 3056, THE TWO MUST COINCIDE
 PLEASE CORRECT.
  
 2) HAVE NEW ENERGY CAL'S. SIGNED BY
 OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2
  
 3) SUBMIT A COMPLETE SET OFMANUAL J
 CALCULATIONS, PER 2004 FBC
 13-607.1.ABC.1 .
  
 4) SHOW A/C SYSTEM'S SENSIBLE BTU'S AND
 TOTAL BTU'S ON MECH. SCHEDULE.
  
 5) MECH. PLANS ARE SHOWING TWO RETURN
 AIR GRILLS FOR EXISTING BEDROOM #2,
 PLEASE CORRECT AND SHOW CORRECT SIZE OF
 RETURN AIR DUCT.
  
 6) RETURN ARI TRANSFER DUCT TO EXISTING
 BEDROOM #3 IS TO SMALL, SEE NOTE #7.
  
 7) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  