| Date |
Text |
| 2005-06-16 00:00:00 | |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE RISER DIAGRAM APPEARS TO INDICATE |
| | #1 CU. AND A #6 GROUND IN THE CONDUIT |
| | PRESUMABLY COMING FROM THE METER, |
| | ALTHOUGH THIS IS NOT CLEAR BECAUSE THE |
| | LINE LEAVING THE METER IS NOT LABLED AT |
| | ALL. THE #1 CONDUCTORS ARE TOO SMALL FOR |
| | A 200 AMP OCP. SEE 310.15(B)(6).ALSOTHE |
| | GEC NEEDS TO BE SHOWN SEPARATE FROM THE |
| | FEED, AND THE #2 WHILE NOT A VIOLATION, |
| | IS A RATED GEC FOR A 300 TO 500 AMP |
| | SERVICE. THE ELECTRICAL CONTRACTOR COULD |
| | FURNISH INSIGHT AS TO PRACTICAL |
| | INSTALLATION. REVISE DRAWING TO SHOW |
| | COMPLIANCE WITH 215.5. INDICATE THE |
| | CONDUIT AND WIRE SIZE FROM THE METER TO |
| | THE PANEL. |
| | |
| | 2} THE FUTURE POOL HEATER IS CALCULATED |
| | AT 1200 VA. PLEASE VERIFY. |
| | |
| | 3} THE GENERAL LIGHTING CIRCUIT BREAKERS |
| | ARE LISTED AS 4 POLE. PLEASE CLARIFY. |
| | |
| | 4}PLEASE SUBMIT AIC RATINGS FOR ALL |
| | NEW SERVICE EQUIPMENT BEING INSTALLED. |
| | MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 5} 3} SHOW LIGHTING PER ARTICLE |
| | 210.70(A)(1,2&3). |
| | |
| | 4} SMOKE DETECTORS ARE REQUIRED PER |
| | 8-1.4.1.6 NFPA-72. |
| | |
| | 5} PER ARTICLE 3401.7.2.6 OF THE FLORIDA |
| | BUILDING CODE THE WIRING IN THE ENTIRE |
| | HOUSE, INCLUDING OUTSIDE RECEPTACLES, |
| | MUST BE MADE TO COMPLY WITH NFPA-70, |
| | 2002, SHOW ON PLAN. |
| | |
| | 6} SHW THE LOCATIONS OF ALL SERVICE |
| | EQUIPMENT ON THE PLAN. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |