 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE RISER DIAGRAM APPEARS TO INDICATE
 #1 CU. AND A #6 GROUND IN THE CONDUIT
 PRESUMABLY COMING FROM THE METER,
 ALTHOUGH THIS IS NOT CLEAR BECAUSE THE
 LINE LEAVING THE METER IS NOT LABLED AT
 ALL. THE #1 CONDUCTORS ARE TOO SMALL FOR
 A 200 AMP OCP. SEE 310.15(B)(6).ALSOTHE
 GEC NEEDS TO BE SHOWN SEPARATE FROM THE
 FEED, AND THE #2 WHILE NOT A VIOLATION,
 IS A RATED GEC FOR A 300 TO 500 AMP
 SERVICE. THE ELECTRICAL CONTRACTOR COULD
 FURNISH INSIGHT AS TO PRACTICAL
 INSTALLATION. REVISE DRAWING TO SHOW
 COMPLIANCE WITH 215.5. INDICATE THE
 CONDUIT AND WIRE SIZE FROM THE METER TO
 THE PANEL.
  
 2} THE FUTURE POOL HEATER IS CALCULATED
 AT 1200 VA. PLEASE VERIFY.
  
 3} THE GENERAL LIGHTING CIRCUIT BREAKERS
 ARE LISTED AS 4 POLE. PLEASE CLARIFY.
  
 4}PLEASE SUBMIT AIC RATINGS FOR ALL
 NEW SERVICE EQUIPMENT BEING INSTALLED.
 MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 5} 3} SHOW LIGHTING PER ARTICLE
 210.70(A)(1,2&3).
  
 4} SMOKE DETECTORS ARE REQUIRED PER
 8-1.4.1.6 NFPA-72.
  
 5} PER ARTICLE 3401.7.2.6 OF THE FLORIDA
 BUILDING CODE THE WIRING IN THE ENTIRE
 HOUSE, INCLUDING OUTSIDE RECEPTACLES,
 MUST BE MADE TO COMPLY WITH NFPA-70,
 2002, SHOW ON PLAN.
  
 6} SHW THE LOCATIONS OF ALL SERVICE
 EQUIPMENT ON THE PLAN.
  