| Plan Review Notes For Permit 05020987 |
| Permit Number |
05020987 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-01 00:00:00 | MECH. PLAN REVIEW. | | | | | | 1. BUILDING REQUIRES FLORIDA ENERGY | | | EFFICIENCY REPORT. | | | 2. A/C PLAN DOES NOT REFLECT RETURN | | | AIR TO A.U.H. OR R/A OUT OF BEDROOMS / | | | DRYER VENT / AND BEDROOM 2. A/C. | | | 3. LOCATION OF CONDENSING UNIT NOT | | | REFLECTED ON A/C PLAN. | | | 4. A.H.U. REQUIRES SAFE PAN UNDER UNIT | | | W/ FLOAT S.W. . FBC/M 307.2.3AND | | | CONDENSATE PIPING WITH TURMINATION POINT | | | TO BE REFLECTED ON A/C PLAN. | | | | | | PAT RAFTER 561/805/6728 OR 805/6719. | | | PLEASE CALL IF THEAR ANY QUESTION. |
|