2005-03-01 00:00:00MECH. PLAN REVIEW.
  
 1. BUILDING REQUIRES FLORIDA ENERGY
 EFFICIENCY REPORT.
 2. A/C PLAN DOES NOT REFLECT RETURN
 AIR TO A.U.H. OR R/A OUT OF BEDROOMS /
 DRYER VENT / AND BEDROOM 2. A/C.
 3. LOCATION OF CONDENSING UNIT NOT
 REFLECTED ON A/C PLAN.
 4. A.H.U. REQUIRES SAFE PAN UNDER UNIT
 W/ FLOAT S.W. . FBC/M 307.2.3AND
 CONDENSATE PIPING WITH TURMINATION POINT
 TO BE REFLECTED ON A/C PLAN.
  
 PAT RAFTER 561/805/6728 OR 805/6719.
 PLEASE CALL IF THEAR ANY QUESTION.