| Plan Review Notes For Permit 05020987 |
| Permit Number |
05020987 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-28 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} SHOW THE LOCATION OF THE NEW SUB | | | PANEL ON THE PLAN. | | | | | | 2} IF EXISTING SERVICE AND SUBPANEL ARE | | | ON THE SAME BUILDING WHY DOES THE | | | SUBPANEL HAVE A GEC? COMPLY WITH 250.32. | | | | | | 3} SHOW LIGHTING PER ARTICLE | | | 210.70(A)(1,2&3). | | | | | | 4} SMOKE DETECTORS ARE REQUIRED PER | | | 8-1.4.1.6 NFPA-72. | | | | | | 5} PER ARTICLE 3401.7.2.6 OF THE FLORIDA | | | BUILDING CODE THE WIRING IN THE ENTIRE | | | HOUSE, INCLUDING OUTSIDE RECEPTACLES, | | | MUST BE MADE TO COMPLY WITH NFPA-70, | | | 2002, SHOW ON PLAN. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | |
|