| Plan Review Notes For Permit 05020982 |
| Permit Number |
05020982 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-22 00:00:00 | | | | PLEASE PROVIDE AIC CALCULATIONS AND | | | INDICATE THE AIC RATING OF THE EQUIPMENT | | | PER 110.9 & 10.NEC. | | | | | | PLANS MUST CONTAIN THE PRINTED NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE PLANS PER 104.2.1 FBC. | | | | | | PLEASE ADD THESE ITEMS TO PLANS AND | | | RESUBMIT FOR REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|