Plan Review Notes
Plan Review Notes For Permit 05020887
Permit Number 05020887
Review Stop E
Sequence Number 1
Notes
Date Text
2005-02-25 00:00:00*************** UNSAT ***********
  
 1)NOTE: PLEASE SEE ALL PLANS WHICH
 CONTAIN TITLE BLOCKS FOR ARCH'S ENG'S
 MUST BE SIGNED,SEALED AND DATED.
 FS 481.221,471.025
 PLEASE BE SURE ARCH/ENG'S TITLE BLOCK
 INCLUDE ALL INFORMATION AS SETFORTH IN
 FAC 61G1-16.004,61G15-23.002.
 PLEASE SEE MISSING LICENSE INFORMATION
 ETC.
  
 2)NOTE: PLEASE PROVIDE CIRCUIT #S ON
 PLANS TO EXISTING/NEW PANELS.
 PLEASE ALSO INCLUDE BRANCH CIRCUIT SIZE
 ALONG WITH CONDUCTOR SIZES.
  
 3)NOTE: PLEASE PROVIDE A DISCONNECTING
 MEANS AT THESE "DEATCHED" BOOTH UNITS.
 225.31
 THIS CAN BE AS LITTLE AS A SP SWITCH FOR
 ONE CIRCUIT.
  
 4)NOTE: PLEASE SEE BLDG REVIEW COMMENTS,
 CITY PLACE PLANS ARE TO BE STAMPED AND
 SIGNED BY CITY PLACE.
  
 5)NOTE: PLEASE ALSO SEE FBC 104.2.1, ALL
 PLANS ARE TO HAVE THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGN.
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  