Plan Review Notes
Plan Review Notes For Permit 05020853
Permit Number 05020853
Review Stop M
Sequence Number 2
Notes
Date Text
2005-05-04 00:00:00PROVISO:
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR SYSTEMS WHICH HAS THE
 DESIGN CAPACITY GREATER THAN 2,000 CFM
 OR WHEN THE AGGREATEAIR EXCEEDS 2,000
 CFM, PER 2001 FBC(M)606.2.1 & 606.2.5.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.