| Plan Review Notes For Permit 05020853 |
| Permit Number |
05020853 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-05-04 00:00:00 | PROVISO: | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | REQUIRED FOR SYSTEMS WHICH HAS THE | | | DESIGN CAPACITY GREATER THAN 2,000 CFM | | | OR WHEN THE AGGREATEAIR EXCEEDS 2,000 | | | CFM, PER 2001 FBC(M)606.2.1 & 606.2.5. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|