Plan Review Notes
Plan Review Notes For Permit 05020853
Permit Number 05020853
Review Stop M
Sequence Number 1
Notes
Date Text
2005-02-22 00:00:00PROVISO:
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR SYSTEMS WITH THE DESIGN
 CAPACITY GREATER THAN 2,000 CFM OR WHEN
 THE AGGREATE AIR EXCEEDS 2,000 CFM, PER
 2001 FBC(M)606.2.1 & 606.2.5,
 RESPECTIVELY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.