Plan Review Notes
Plan Review Notes For Permit 05020800
Permit Number 05020800
Review Stop E
Sequence Number 2
Notes
Date Text
2005-03-29 00:00:00******* UNSAT *******
  
 1)NOTE: PLEASE SEE POOL WIRING DIAGRMA
 DOES NOT INCLUDE ANY WIRING SIZES,
 CONDUIT SIZES ETC FOR NEW POOL HEATER.
 "NOTE" MENTIONS, "TO ELECTRICAL PANEL
 WITH SEPARATE CIRCUIT FOR MOTOR AND LT"
 PLEASE VERIFY HOW HEATER WILL BE FED?
  
 2)NOTE: PLEASE INLCUDE THE MANUFACTURE'S
 SPEC'S FOR NEW HEAT PUMP.
 PLEASE SURE SPECS INCLUDE A LISTING FROM
 A NRTL.
  
 3)NOTE: PLEASE SEE ONLY ONE MOTOR SHOWN
 ON WIRING DIAGRAM.
  
 4)NOTE: PLEASE SEE BLOWER NOT SHOWN WITH
 ANY WIRE SIZES?
 PLEASE ALSO BLOWER NOT SHOWN ON LOAD
 CALCS.
  
 5)NOTE: PLEASE SEE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%. (POOL
 MOTOR/HEAT PUMP) 215.3,2230.42 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  