| Plan Review Notes For Permit 05020800 |
| Permit Number |
05020800 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-03-29 00:00:00 | ******* UNSAT ******* | | | | | | 1)NOTE: PLEASE SEE POOL WIRING DIAGRMA | | | DOES NOT INCLUDE ANY WIRING SIZES, | | | CONDUIT SIZES ETC FOR NEW POOL HEATER. | | | "NOTE" MENTIONS, "TO ELECTRICAL PANEL | | | WITH SEPARATE CIRCUIT FOR MOTOR AND LT" | | | PLEASE VERIFY HOW HEATER WILL BE FED? | | | | | | 2)NOTE: PLEASE INLCUDE THE MANUFACTURE'S | | | SPEC'S FOR NEW HEAT PUMP. | | | PLEASE SURE SPECS INCLUDE A LISTING FROM | | | A NRTL. | | | | | | 3)NOTE: PLEASE SEE ONLY ONE MOTOR SHOWN | | | ON WIRING DIAGRAM. | | | | | | 4)NOTE: PLEASE SEE BLOWER NOT SHOWN WITH | | | ANY WIRE SIZES? | | | PLEASE ALSO BLOWER NOT SHOWN ON LOAD | | | CALCS. | | | | | | 5)NOTE: PLEASE SEE ALL CONTINUOUS LOADS | | | ARE TO BE SHOWN AT 125%. (POOL | | | MOTOR/HEAT PUMP) 215.3,2230.42 ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|