| 2006-02-17 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} SINCE THE SERVICE HAS NOW BEEN |
| | CHANGED TO INCLUDE THE THE COTTAGE |
| | PLEASE SUBMIT ALL PANEL SCHEDULES SO |
| | THAT BRANCH CIRCUIT COMPLIANCE CAN BE |
| | DETERMINED. |
| | |
| | 2} THE HOT TUB MUST BE INCLUDED IN THE |
| | CALCULATIONS. 220.31. |
| | |
| | 3} INDICATE THE SIZE OF THE GROUNDING |
| | ELECTRODE CONDUCTOR(S), AND INDICATE |
| | GROUNDING ELECTRODE SYSTEM PER 250.52. |
| | |
| | 4} 110.9 INTERRUPTING RATING. |
| | EQUIPMENT INTENDED TO INTERRUPT CURRENT |
| | AT FAULT LEVELS SHALL HAVE AN |
| | INTERRUPTING RATING SUFFICIENT FOR THE |
| | NOMINAL CIRCUIT VOLTAGE AND THE CURRENT |
| | THAT IS AVAILABLE AT THE LINE TERMINALS |
| | OF THE EQUIPMENT. |
| | EQUIPMENT INTENDED TO INTERRUPT CURRENT |
| | AT OTHER THAN FAULT LEVELS SHALL HAVE AN |
| | INTERRUPTING RATING AT NOMINAL CIRCUIT |
| | VOLTAGE SUFFICIENT FOR THE CURRENT THAT |
| | MUST BE INTERRUPTED. INDICATE RATING ON |
| | PLAN. |
| | |
| | 5} A SMOKE DETECTOR IS REQUIRED AT THE |
| | STAIRWAY ON THE FIRST FLOOR TO COMPLY |
| | WITH NFPA-72 AND FBC 8-1.4.2. SEE |
| | PERMITED SET OF PLANS. |
| | |
| | 6} THE PERSON RESPONSIBLE FOR THE PLAN |
| | MUST SIGN SAME.104.2.1 FBC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |