| Plan Review Notes For Permit 05020761 |
| Permit Number |
05020761 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-03 00:00:00 | PROVISO: | | | PLEASE PROVIDE REVISED PLANS PRIOR TO | | | INSPECTION, INCLUDE THE FOLLOWING | | | INFORMATION: | | | 1.SEVERAL DUCT SIZES AND A GRILLE SIZE | | | MISSING (SEE PLAN SHEET M1). | | | 2.PROVIDE COMBUSTION AIR CALCULATIONS | | | IN ACCORDANCE WITH 2001 FBC(M) CHAPTER 7 | | | 3.PLAN INDICATES MAKE-UP AIR IN THE | | | LAUNDRY ROOM, OPENINGS SHALL COMPLY WITH | | | 2001 FBC(M)704 & 704.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|