Plan Review Notes
Plan Review Notes For Permit 05020761
Permit Number 05020761
Review Stop B
Sequence Number 1
Notes
Date Text
2005-03-03 00:00:00 
 BUILDING PLAN REVIEW: FAILED
  
 1. CALCULATED VALUE OF HOUSE FOR PERMIT
 FEES ADJUSTED. ADDITIONAL FEES OF
 $630.04 DUE BEFORE A PERMIT CAN BE
 ISSUED.
  
 2. A NOTICE OF COMMENCEMENT MUST BE
 FILED AT THE COUNTY CLERKS OFFICE AND A
 COPY OF THE RECORDED NOC SUBMITTED.
  
 3. PLANS MUST BE TAKEN TO PBC AND IMPACT
 FEES PAID. A COPY OF THE RECEIPT AND
 STAMPED PLANS MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4. SHEET A-1 STATES WIND LOAD AS PER
 1997 STANDARD BUILDING CODE. MUST BE FBC
 2001.
  
 5.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 WWW.FLORIDABUILDING.ORG.
 SUBMIT FL PRODUCT APPROVALS FOR THE
 FOLLOWING:
 WINDOWS
 DOORS
 GARAGE DOORS
 STORM PANELS
 ROOF SYSTEM
 STRUCTURAL COMPONENTS (TRUSS STRAPS,
 ETC)
  
 6. DOOR LEADING TO GARAGE FROM LIVING
 AREA MUST BE SOLID OR INSULATED.
  
 7. SUBMIT A COPY OF PAGE 1 OF THE
 FLORIDA ENERGY CODE.WE HAVE TO SUBMIT
 IT TO THE STATE.
  
 8. STORM PANEL INSTALLATION SCHEDULE
 MUST BE SUBMITTED. A SAMPLE IS ATTACHED.
  
 9. LIST EACH OPENING PER PLANS WITH TYPE
 OF PANEL, ANCHOR TYPE, ETC.
  
 10. FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713
  
  