Plan Review Notes
Plan Review Notes For Permit 05020756
Permit Number 05020756
Review Stop M
Sequence Number 3
Notes
Date Text
2005-10-20 00:00:00*** DENIED ***
 1) A/C EQUIPMENT LIST ON PLANS SHOWS A/C
 #1 10.25 SEER, #2 10.25 SEER, #3 10.25
 SEER, AND #4 10.0 . ENERGY CAL'S. ON
 FLLE CALL FOR A/C #1 12.25 SEER, #2
 12.50 SEER, #3 12.00 SEER, AND #4 10.00
 SEER. THE PLANS MUST MATCH THE ENERGY
 CAL'S. .
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.