2005-03-25 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1} PANEL "C" MUST BE GROUNDED PER
 250.32.
  
 2} THE GREOUNDING ELECTRODE CONDUCTOR
 FOR THE SERVICE MUST BE A MINIMUM #1/0CU
 PER 250.66.
  
 3} THE AHU'S HAVE 30 AMP DISCONNECTS
 WITH #12 WIRE ON THE RISER.THEY HAVE 60
 AMP OCP WITH #12 WIRE AND ARE RATED AT
 9.6KVA ON THE PANEL SCCHEDULE, PLEASE
 CORRELATE.
  
 4} THE RISER SHOWS PANEL "C" BEING FED
 FROM PANEL "B", BUT THERE IS NO FEED FOR
 SAME IN PANEL SCHEDULE "B".
  
 5} PLEASE NOTE THAT THE TERM "OUTLETS"
 IN 210.12 REGARDING BEDROOMS ALSO
 INCLUDES SMOKE DETECTORS, LIGHTS,FANS, "
 ALL 15 & 20 AMP BRANCH CIRCUITS".
  
 6} THE GUEST ROOM (106) NEEDS A
 RECEPTACLE TO COMPLY WITH 210.52(A).
  
 7} THE CABANA BATHROOM RECEPTACLE MUST
 COMPLY WITH 210.11(3)(C). INDICATE SAME
 ON PANEL SCHEDULE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  