| Plan Review Notes For Permit 05020756 |
| Permit Number |
05020756 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-03-25 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | | | | 1} PANEL "C" MUST BE GROUNDED PER | | | 250.32. | | | | | | 2} THE GREOUNDING ELECTRODE CONDUCTOR | | | FOR THE SERVICE MUST BE A MINIMUM #1/0CU | | | PER 250.66. | | | | | | 3} THE AHU'S HAVE 30 AMP DISCONNECTS | | | WITH #12 WIRE ON THE RISER.THEY HAVE 60 | | | AMP OCP WITH #12 WIRE AND ARE RATED AT | | | 9.6KVA ON THE PANEL SCCHEDULE, PLEASE | | | CORRELATE. | | | | | | 4} THE RISER SHOWS PANEL "C" BEING FED | | | FROM PANEL "B", BUT THERE IS NO FEED FOR | | | SAME IN PANEL SCHEDULE "B". | | | | | | 5} PLEASE NOTE THAT THE TERM "OUTLETS" | | | IN 210.12 REGARDING BEDROOMS ALSO | | | INCLUDES SMOKE DETECTORS, LIGHTS,FANS, " | | | ALL 15 & 20 AMP BRANCH CIRCUITS". | | | | | | 6} THE GUEST ROOM (106) NEEDS A | | | RECEPTACLE TO COMPLY WITH 210.52(A). | | | | | | 7} THE CABANA BATHROOM RECEPTACLE MUST | | | COMPLY WITH 210.11(3)(C). INDICATE SAME | | | ON PANEL SCHEDULE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|