1 |
|
| Notes |
| Date |
Text |
| 2005-02-22 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THERE ARE NO MAIN DISCONNECTS SHOWN | | | FOR PANELS "A" & "B", THE RISER ONLY | | | SHOWS A METERAS DOES THE PLAN. ALSO | | | PANELS ARE LISTED AS MLO, THEY MUST HAVE | | | A DISCONNECTING MEANS. | | | | | | 2} PLEASE SEE THAT THE FEEDERS FOR THE | | | AHU'S AND CU'S ARE INCORRECT ON THE | | | RISER DIAGRAM, ALSO THE OCP'S. | | | | | | 3} A RECEPTACLE NEEDS TO BE ADDED TO THE | | | FRONT OUTSIDE PER 210.52(E). | | | | | | 4} RECEPTACLES NEED TO BE ADDED TO THE | | | LIBRARY PER 210.52(A). | | | | | | 5} THE KITCHEN COUNTERTOP RECEPTACLES DO | | | NOT COMPLY WITH 210.52(C) SPACING | | | REQUIREMENTS. | | | | | | 6} BEDROOM #3 NEEDS A RECEPTACLE ADDED | | | TO COMPLY WITH 210.52(A)(2). | | | | | | 7} THE ARHITECTS TITLE BLOCK NEEDS THE | | | FIRM LICENSE # PER 61G1-16.004(2), FAC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|