| 2005-04-01 00:00:00 | DENIED | | | | | | 1) THE ENERGY CALC. FORMS ARE INCORRECT. | | | THEY DO NOT LIST THE 2X6 WOOD FRAME | | | EXTERIOR WALLS AND LIST R19 IN THE | | | CEILINGS, NOT R30 AS SPECIFIED ON THE | | | PLANS. | | | | | | 2) THE CONNECTOR SCHEDULE SCHEDULE LISTS | | | A SIMPSON HDSA ANCHOR TYPE. IS THIS | | | SUPPOSE TO BE A HD5A? INDICATE HOW THE | | | UPLIFT VALUE WAS DETERMINED. | | | | | | 3) ROOF TRUSS MG1 HAS AN UPLIFT THAT | | | EXCEEDS THE CAPACITY OF THE SIMPSON H10 | | | THAT IS SPECIFIED FOR IT. | | | | | | 4) ROOF GIRDER TRUSS GR3 IS INDICATED AS | | | A 2 MEMBER TRUSS ON THE TRUSS LAYOUT AND | | | THE PLANS SPECIFY A 4 MEMBER TRUSS AT | | | THIS LOCATION. | | | | | | 5) SPECIFY THE MECHINICAL CONNECTIONS | | | FOR ROOF TRUSSES GR2 AND GR3 AT THE | | | INTERIOR MASONRY WALLS. | | | | | | 6) SUBMIT THE INSTALLATION INSTRUCTIONS | | | FOR THE ROOF SHINGLES. | | | | | | 7) SUBMIT THE NOA FOR THE GLASS BLOCK, | | | WHICH CONTAINS THE INSTALLATION | | | INSTRUCTIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | | | | |
|