Plan Review Notes
Plan Review Notes For Permit 05020746
Permit Number 05020746
Review Stop B
Sequence Number 1
Notes
Date Text
2005-04-01 00:00:00DENIED
  
 1) THE ENERGY CALC. FORMS ARE INCORRECT.
 THEY DO NOT LIST THE 2X6 WOOD FRAME
 EXTERIOR WALLS AND LIST R19 IN THE
 CEILINGS, NOT R30 AS SPECIFIED ON THE
 PLANS.
  
 2) THE CONNECTOR SCHEDULE SCHEDULE LISTS
 A SIMPSON HDSA ANCHOR TYPE. IS THIS
 SUPPOSE TO BE A HD5A? INDICATE HOW THE
 UPLIFT VALUE WAS DETERMINED.
  
 3) ROOF TRUSS MG1 HAS AN UPLIFT THAT
 EXCEEDS THE CAPACITY OF THE SIMPSON H10
 THAT IS SPECIFIED FOR IT.
  
 4) ROOF GIRDER TRUSS GR3 IS INDICATED AS
 A 2 MEMBER TRUSS ON THE TRUSS LAYOUT AND
 THE PLANS SPECIFY A 4 MEMBER TRUSS AT
 THIS LOCATION.
  
 5) SPECIFY THE MECHINICAL CONNECTIONS
 FOR ROOF TRUSSES GR2 AND GR3 AT THE
 INTERIOR MASONRY WALLS.
  
 6) SUBMIT THE INSTALLATION INSTRUCTIONS
 FOR THE ROOF SHINGLES.
  
 7) SUBMIT THE NOA FOR THE GLASS BLOCK,
 WHICH CONTAINS THE INSTALLATION
 INSTRUCTIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  