Plan Review Notes
Plan Review Notes For Permit 05020722
Permit Number 05020722
Review Stop P
Sequence Number 1
Notes
Date Text
2005-02-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SUBMIT A SANITARY RISER DIAGRAM IN
 ISOMETRIC FORM SHOWING ALL PIPE SIZES,
 VENTS, CLEANOUTS, AND INDICATE POINT OF
 CONNECTION. SECTION 1-4.3.1.1.
 2) SUBMIT A WATER RISER DIAGRAM
 ISOMETRIC SHOWING ALL PIPE SIZES,
 VALVES, WATER HAMMER ARRESTORS REQUIRED
 BY SECTION 604.9, AND INDICATE POINT OF
 CONNECTION. SECTION 104.2.1.1.
 3) SUBMIT A ACCESSIBLITY DETAIL FOR THE
 TOILET ROOM SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 4) SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL
 SUBSTECTIONS. (FORWARD APPROACH
 REQUIRED)
 5) WATER COOLER SHALL COMPLY WITH
 ARI-1010 PER SECTION 410.1. SUBMIT
 MANUF. SPECIFICATION SHEET SHOWING
 COMPLIANCE.
 6) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO PARKING GARAGE OFFICE.
 SECTION 608.13.2.
  