| 2005-02-17 00:00:00 | ************ UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE FS 471.003(2)(H)2A. |
| | PLANS FOR NEW ELECTRICAL SYSTEMS FOR |
| | 277/480V MUST BE DONE AND SIGNED,DATED |
| | AND SEALED BY AN PE. |
| | |
| | 2)NOTE: PLEASE PROVIDE GROUNDING FOR NEW |
| | TRANSFORMER. PLEASE SEE 250.30 |
| | |
| | 3)NOTE: PLEASE SEE PLANS APPEAR TO SHOW |
| | TRANSFORMER IN THE CLEARENCE ARE |
| | REQUIRED FOR PANEL PER 110.26? |
| | |
| | 4)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS (LIGHTING) AND CORRELATE WITH THE |
| | SUBMITTED PANEL SCHEDULE. |
| | PLEASE ALSO SEE 700.12E |
| | |
| | 5)NOTE: PLEASE SEE CONDUCTORS SHOWN FOR |
| | FEED FROM NEW 60A DISC TO TRANSFORMER. |
| | PLEASE SEE EQUIPMENT GROUNDING CONDUCTOR |
| | APPEARS TO BE SHOWN AS A 4/0? |
| | PLEASE VERIFY. |
| | 250.122 |
| | |
| | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | AIC RATING SHOWN FOR PANEL , NEEDED FOR |
| | MAIN DISC. |
| | |
| | 7)NOTE: PLEASE SEE PANEL INDICATES |
| | 270V/480V. 270V APPEARS TO BE A |
| | MISPRINT. |
| | |
| | 8)NOTE: PLEASE PROVIDE CONDUCTOR SIZES |
| | AND LOAD CALCULATIONS FOR EXISTING |
| | WIREWAY IN WHICH NEW FEED IS BEING |
| | TAPPED FROM. |
| | 220,215.5 |
| | |
| | 9)NOTE: PLEASE SEE MISSING GFI FOR COND |
| | UNIT SERVICE RECEPT. 210.63 |
| | |
| | 10)NOTE: PLEASE SHOW LOCATION OF NEW |
| | DISC AT OFFICE BLDG ON LINE SIDE OF |
| | TRANSFORMER. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |