Plan Review Notes
Plan Review Notes For Permit 05020722
Permit Number 05020722
Review Stop B
Sequence Number 1
Notes
Date Text
2005-02-17 00:00:00PERMIT #05020722
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) IMPACT FEES MAY BE DUE.THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED
 TO THE APPLICATION.233-5025.DOR TO
 PROVIDE AREA CALCULATIONS (ADDITION
 SQUARE FOOTAGE) ON THE PLAN.
  
 2.) THE OWNER ON THE APPLICATION DOESN?T
 MATCH THE OWNER IN OUR RECORDS, SEE
 ATTACHED.
  
 3.) FBC*104.3.1.1, MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS, PLEASE PROVIDE
 OCCUPANCY GROUP, MINIMUM CONSTRUCTION
 TYPE, FIRE SUPPRESSION SYSTEM PLAN,
 OCCUPANCY LOAD.
  
 4.) PROVIDE ENERGY CALCS, FBC13-103.1.
  
 5.) THE BREAK ROOM SINK IS TO COMPLY
 WITH FBC11-4.24.PROVIDE A DETAIL.
  
 6.) PROVIDE DETAILS FOR THE ACCESSIBLE
 BATHROOM (GRAB BARS, SINK, WC, WITH
 DIMENSIONS).
  
 7.) WILL PARKING SPACES BE PROVIDED FOR
 EMPLOYEES?SEE FBC11-4.2(5)(A).
  
 8.) SHOW THE ACCESSIBLE ROUTE, FROM
 ACCESSIBLE PARKING AND FROM THE PUBLIC
 WAY, 11-4.1.2.
  
 9.) PROVIDE A WATERPROOFING DETAIL AT
 THE BASE OF THE WALL, A-A2.1.
  
 10.) PLEASE CLARIFY AS TO WHY YOU
 SPECIFY A 45 MINUTE DOOR AND 1 ? HOUR
 WINDOWS.
  
 11.) D-A2.1 SPECIFIES SMS SCREWS;
 PROVIDE UPLIFT INFORMATION AND SIZE,
 NUMBER OF FASTENERS.
  
 12.) SIMPSON ST22 STRAPS SPECIFIED.
 THIS IS A WOOD CONNECTOR WHICH YOU ARE
 USING IN A METAL STUD APPLICATION.
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED FAC9B72.
  
 13.) SPECIFY THE CONCRETE STRENGTH FOR
 THE CURB, D-A2.1.
  
 14.) SPECIFY THE SIZE OF ALL FRAMING
 MEMBERS AND ATTACHMENTS.SEE ATTACHED
 CEILING SPAN TABLE.
  
 15.) PLYWOOD (COMBUSTIBLE) IS NOT
 ALLOWED IN A TYPE II BUILDING; APPEARS
 ON SEVERAL DETAILS.
  
 16.) THE INTERIOR WALLS AND HEADER
 (A-A2.1, C-A2.1) DO NOT COMPLY WITH THE
 2 HOUR WALL DETAIL PROVIDED (THE TWO
 SHEETS OF DRYWALL MISSING AT THE
 FIREBLOCKING).
  
 17.) D-A2.1, HOW DOES THE BRACING ATTACH
 TO THE DOUBLE T?
  
 18.) D-A2.1, PROVIDE EMBEDMENT FOR THE
 EXPANSION ANCHOR AND THE #5 INTO THE
 SLAB.
  
 19.) PROVIDE CLEARANCE INFORMATION FOR
 THE BIFOLD DOOR, FBC11-4.13.5.
  
 20.) PROVIDE A BACKING DETAIL FOR THE
 GRAB BARS.
  
 21.) PRODUCT APPROVALS AND TEST
 REPORTS/INSTALLATION INSTRUCTIONS
 REQUIRED FOR THE IMPACT PROTECTION, DOOR
 AND WINDOWS.STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.
  
 21.) IMPACT PROTECTION REQUIRED,
 FBC1606.1.4.
  
 22.) PROVIDE DESIGN INFORMATION ON THE
 PLAN, FBC1606.1.7.
  
 23.) WHERE WILL THE SHUTTERS BE STORED?
 IF THEY ARE STORED VERTICALLY, PROVIDE A
 RACK DETAIL.
  
 24.) SPECIFY ALL ATTACHMENTS FOR THE
 METAL FRAMING.
  