| Plan Review Notes For Permit 05020649 |
| Permit Number |
05020649 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-12-02 00:00:00 | | | | THE REVISION SUBMITTED ON SHEET A-2 DO | | | NOT REVLECT PRIOR REVISIONS OR THE | | | COMPLETE SCOPE OF WORK PERMITTED. | | | | | | PLEASE PUT ALL ELECTRICAL REVISIONS | | | ,PRIOR AND CURRENT ON ONE SHEET, SHOW | | | ALL WORK IN ENTIRETY. IF ANOTHER SHEET | | | IS NEEDED, GIVE IT A DIFFERENT | | | DESIGNATION. | | | | | | THE #10 GEC ON THE 30 AMP SUB PANEL IS | | | NOT IN COMPLIANCE WITH 250.66, WHICH | | | REQUIRES A #8 MINIMUM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|