2005-12-02 00:00:00 
 THE REVISION SUBMITTED ON SHEET A-2 DO
 NOT REVLECT PRIOR REVISIONS OR THE
 COMPLETE SCOPE OF WORK PERMITTED.
  
 PLEASE PUT ALL ELECTRICAL REVISIONS
 ,PRIOR AND CURRENT ON ONE SHEET, SHOW
 ALL WORK IN ENTIRETY. IF ANOTHER SHEET
 IS NEEDED, GIVE IT A DIFFERENT
 DESIGNATION.
  
 THE #10 GEC ON THE 30 AMP SUB PANEL IS
 NOT IN COMPLIANCE WITH 250.66, WHICH
 REQUIRES A #8 MINIMUM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  