Plan Review Notes
Plan Review Notes For Permit 05020557
Permit Number 05020557
Review Stop B
Sequence Number 1
Notes
Date Text
2005-03-01 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. DRAWINGS SUBMITTED SHOW 20 WINDOWS IN
 HOUSE.PERMIT STATES ONLY REPLACING 12
 WINDOWS.MARK THE WINDOWS ON THE
 DRAWINGS TO BE REPLACED.
  
 2. ACCORDIING TO FBC2001 WHEN REPLACING
 OVER 25% OF GLASS AREA IN STRUCTURE
 HURRICANE PROTECTION IS REQUIRED. IF
 THERE ARE EXISTING SHUTTERS NOTE ON
 APPLICATION.IF NO SHUTTERS SUBMIT THE
 PRODUCT APPROVALS & INSTALLATION
 SCHEDULE FOR THE STORM PANELS. THE VALUE
 OF THE PERMIT MUST BE INCREASED. IF THE
 TOTAL VALUE IS OVER $2500. A NOTICE OF
 COMMENCEMENT RECORDED AT THE COUNTY
 CLERKS OFFICE WILL BE REQUIRED.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713