Plan Review Notes
Plan Review Notes For Permit 05020538
Permit Number 05020538
Review Stop E
Sequence Number 1
Notes
Date Text
2005-02-18 00:00:00 
 PLEASE NOTE THE FOLLOWING REQUIREMENTS
 FOR CODE COMPLIANCE MUST REFLECT ON
 DRAWINGS.
  
 1} THE DISCONNECTS FOR THE SERVICE
 EQUIPMENT SHALL BE GROUPED PER 230.72.
  
 2} INDICATE THE SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR PER 250.66.
  
 3} INDICATE THE AIC RATING OF THE
 SERVICE EQUIPMENT PER 110.9 & 110.10.
  
 4} THE PANEL ON THE SECOND FLOOR MAY NOT
 BE LOCATED IN THE CLOSET. SEE 110.26 AND
 408.7 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  