| Plan Review Notes For Permit 05020538 |
| Permit Number |
05020538 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-18 00:00:00 | | | | PLEASE NOTE THE FOLLOWING REQUIREMENTS | | | FOR CODE COMPLIANCE MUST REFLECT ON | | | DRAWINGS. | | | | | | 1} THE DISCONNECTS FOR THE SERVICE | | | EQUIPMENT SHALL BE GROUPED PER 230.72. | | | | | | 2} INDICATE THE SIZE OF THE GROUNDING | | | ELECTRODE CONDUCTOR PER 250.66. | | | | | | 3} INDICATE THE AIC RATING OF THE | | | SERVICE EQUIPMENT PER 110.9 & 110.10. | | | | | | 4} THE PANEL ON THE SECOND FLOOR MAY NOT | | | BE LOCATED IN THE CLOSET. SEE 110.26 AND | | | 408.7 NEC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|