Plan Review Notes
Plan Review Notes For Permit 05020451
Permit Number 05020451
Review Stop E
Sequence Number 1
Notes
Date Text
2005-02-22 00:00:00 
 THERE ARE TWO RECEPTACLES IN THE BEDROOM
 AND ONE IN THE FAMILY TO BE ADDED FOR
 COMPLIANCE WITH 210.52(A)(1) & (2).
  
 THE LOAD CALCULATIONS DO NOT INCLUDE THE
 ADDITIONAL AHU TO BE INSTALLED. IT IS
 OBVIOUS THAT THE EXISTING SERVICE IS NOT
 LARGE ENOUGH TO SUPPORT THE ADDITIONAL
 LOAD. PLEASE SUBMIT PLANS FOR A SERVICE
 CHANGE INCLUDING RISER DIAGRAM AND AIC
 CALCULATIONS PER 110.9 & 10., IF
 ADDITIONAL LOADS WARRANT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  