| Plan Review Notes For Permit 05020451 |
| Permit Number |
05020451 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-22 00:00:00 | | | | THERE ARE TWO RECEPTACLES IN THE BEDROOM | | | AND ONE IN THE FAMILY TO BE ADDED FOR | | | COMPLIANCE WITH 210.52(A)(1) & (2). | | | | | | THE LOAD CALCULATIONS DO NOT INCLUDE THE | | | ADDITIONAL AHU TO BE INSTALLED. IT IS | | | OBVIOUS THAT THE EXISTING SERVICE IS NOT | | | LARGE ENOUGH TO SUPPORT THE ADDITIONAL | | | LOAD. PLEASE SUBMIT PLANS FOR A SERVICE | | | CHANGE INCLUDING RISER DIAGRAM AND AIC | | | CALCULATIONS PER 110.9 & 10., IF | | | ADDITIONAL LOADS WARRANT. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|