| 2005-03-07 00:00:00 | DENIED |
| | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT |
| | SHALL BE RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSE AND A COPY SUBMITTED TO THIS |
| | OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| | BLANK FORMS ARE AVAILABLE FROM THIS |
| | OFFICE. |
| | NOTE: THE NOTICE OF COMMENCEMENT MUST BE |
| | RE-RECORDED IF THE DESCRIBED IMPROVEMENT |
| | OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| | 90 DAYS OF RECORDING. |
| | |
| | 2.BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3.BASED ON SBCCI BUILDING VALUATION |
| | DATA THE VALUATION HAS BEEN CHANGED TO |
| | $56,027.00.ADDITIONAL PERMIT FEES OF |
| | $515.65 ARE DUE. |
| | |
| | 4.SUBMIT TWO COPIES OF PRODUCT |
| | APPROVALS WITH QUALITY ASSURANCE FOR THE |
| | FOLLOWING.ROOFING, WINDOWS, EXTERIOR |
| | DOORS, IMPACT PROTECTION, STRAPS AND |
| | TIE-DOWNS AND LINTELS. |
| | ALL PRODUCT APPROVALS SUBMITTED SHALL |
| | HAVE THE FOLLOWING ATTACHED. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 5.SAFTEY GLAZING REQUIRED AT WINDOW AT |
| | TUB LOCATION FBC 2405.2.1 |
| | |
| | 6.SUBMIT 2 COPIED OF A SITE PLAN |
| | SHOWING ROOM ADDITION AND ALL BUILDINGS |
| | ON PROPERTY. |
| | |
| | 7.SUBMIT 2 COPIES OF ENERGY CALCS. |
| | |
| | 8.ROOF SHEATHING FASTENING SHALL |
| | COMPLY WITH FBC 2306.1.SHOW ON PLANS. |
| | |
| | 9.SHOW SIZE AND LOCATION OF ATTIC |
| | ACCESS.FBC 2309.6 |
| | |
| | 10.FBC 3401.7.1.2.1 SHOW HOW |
| | COMPLIANCE WILL BE MADE FOR THIS SECTION |
| | FOR GFCI OUTLETS AND SMOKE DETECTORS. |
| | |
| | 11.SQUARE FOOTAGE SUBMITTED ON |
| | APPLICATION WAS NOT CORRECT.IT HAS |
| | BEEN REVISED TO 728 SQ. FT. |
| | SHOW ON PLANS EXISTING SQUARE FOOTAGE |
| | AND NEW SQUARE FOOTAGE. |
| | |
| | 12.IMPACT PROTECTION REQUIRED FOR NEW |
| | WINDOWS AND DOORS. |
| | |
| | 13.NOTE:FINISH GRADE IS 4" ABOVE |
| | GRADE. THIS IS THE MINIMUM ALLOWED. |
| | THE FOOTING IS AT 12" DEEP ALSO A MIN. |
| | ALLOWED.IF THE GRADE ISN'T EXACTLY |
| | CORRECT EITHER THE FOOTING WON'T BE DEEP |
| | ENOUGH OR THE GRADE WILL BE TOO HIGH. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |