| Plan Review Notes For Permit 05020338 |
| Permit Number |
05020338 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-04-24 00:00:00 | ********** UNSAT ********* | | | | | | 1)NOTE: PLEASE SEE REVISION IN TITLE | | | MENTIONS CHNAGED TO SINGLE PHASE | | | SERVICE, HOWEVER PLEASE SEE MAIN IS | | | STILL SHOWN AS 3-PHASE. | | | PLEASE ALSO SEE FEEDERS ON MDP SCHEDULE | | | TO "PP" IS SHOWN FOR 3-PHASE, HOWEVER | | | RISER IS CORRECT FOR SINGLE PHASE. | | | PLEASE MAKE NECESSARY CORRECTTIONS AND | | | CORRELATE. | | | PLEASE ALSO EXPLAIN THE USE OF "XX" AT | | | MCB. | | | 215.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|