2006-04-24 00:00:00********** UNSAT *********
  
 1)NOTE: PLEASE SEE REVISION IN TITLE
 MENTIONS CHNAGED TO SINGLE PHASE
 SERVICE, HOWEVER PLEASE SEE MAIN IS
 STILL SHOWN AS 3-PHASE.
 PLEASE ALSO SEE FEEDERS ON MDP SCHEDULE
 TO "PP" IS SHOWN FOR 3-PHASE, HOWEVER
 RISER IS CORRECT FOR SINGLE PHASE.
 PLEASE MAKE NECESSARY CORRECTTIONS AND
 CORRELATE.
 PLEASE ALSO EXPLAIN THE USE OF "XX" AT
 MCB.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  