| Plan Review Notes For Permit 05020338 |
| Permit Number |
05020338 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-07-28 00:00:00 | ******PASSED/PROVISO****** | | | | | | IT IS UNDERSTOOD THAT THIS BUILDING | | | DOESN'T MEET THE REQUIREMENT FOR A FULL | | | FIRE ALARM SYSTEM. THE PLANS SHOW A FIRE | | | SPRINKLER SYSTEM WHICH IS REQUIRED TO BE | | | MONITORED. THE MONITORING SHALL BE UL | | | CERTIFIED FOR CENTRAL STATION SERVICE | | | AND SEPARATE SHOP DRAWING AND PERMIT IS | | | REQUIRED FOR THE FIRE SPRINKLER SYSTEM. | | | THE DOUBLE CHECK DETECTOR ASSEMBLY FOR | | | THE FIRE SPRINKLER SYSTEM SHALL BE | | | ELECTRONICALLY SUPERVISED IN ADDITION TO | | | SECURED BY CHAIN AND LOCK. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 804-4756 | | | PLAN REVIEW(561) 805-6722 |
|