| 2005-07-27 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05030338 |
| | ADD: 747 NCONGRESS ( CLUBHOUSE) |
| | CONT:WCI |
| | TEL: (561)775-2120 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 3ST REVIEW |
| | ACTION: DENIED |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THE ONLY PRODUCT APPROVALS SUBMITTED FOR |
| | REVIEW ARE THE AMERICAN WARMING & |
| | VENTILATION, WHICH DO NOT REQUIRE THE |
| | STATE APPROVAL. |
| | |
| | 1) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS |
| | B) DOORS SWING & OVERHEAD |
| | C) STORM SHUTTERS IF GLAZED OPENINGS DO |
| | |
| | NOT HAVE LARGE MISSLE IMPACT TESTING |
| | D) TRUSS ANCHORS |
| | E) ROOFING ASSEMBLIES |
| | |
| | 2) MISSING INFORMATION ON THE FACTORY |
| | BUILT FIREPLACE & CHIMNEY? |
| | 2806.1.2 FACTORY BUILT FIREPLACES |
| | SHALL BE TESTED IN ACCORDANCE WITH AND |
| | MEET THE REQUIREMENTS OF UL 127. |
| | CHIMNEYS FOR THE USE WITH FACTORY- |
| | BUILT FIREPLACES SHALL MEET THE |
| | REQUIREMENTS OF UL 127. |
| | |
| | 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | |
| | |
| | |
| | |