| 2005-03-22 00:00:00 | DENIED: | | | 1.AIR SIZING SUMMARY (MANUAL J) FOR | | | AHU'S 1 & 8 INDICATE 5.1 TON UNIT AND | | | THE EQUIPMENT SCHEDULE ON PLAN SHEET | | | M6.1 INDICATE 3 TON UNIT FOR AHU 1 & 8. | | | | | | 2.PLEASE NOTE, MANUAL J CALCULATIONS | | | ARE MISSING FOR AHU 7 & 9. | | | | | | 3.PLAN SHEET M2.1, PLEASE CLARIFY | | | OUTSIDE AIR TO AHU'S 1, 3, 4, 5, 6, & 8. | | | IT APPEARS THAT ONLY UNITS 7, 2, & 9 | | | HAVE OUTSIDE AIR. | | | | | | 4.PLAN INDICATES RETURN AIR JUMPER | | | FROM THE KITCHEN AREA.PLEASE NOTE PER | | | 2001 FBC(M) 403.2.2, AIR MAY BE | | | TRANSFERRED TO KITCHEN AIR FOR THE | | | PURPOSE OF MAKE-UP AIR. AIR FROM THE | | | KITCHEN AIR SHALL NOT BE RECIRCULATED. | | | | | | 5.DUCT SMOKE DETECTORS REQUIRED FOR | | | SYSTEMS WITH THE AGGREGATE CAPACITY IS | | | GREATER THAN 2,000 CFM. | | | | | | 6.FAN SHUTDOW BY DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | IN NORMALLY OCCUPIED AREAS PER 2001 | | | FBC(M) 606.4.1 EXCEPTION #2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|