Plan Review Notes
Plan Review Notes For Permit 05020338
Permit Number 05020338
Review Stop M
Sequence Number 2
Notes
Date Text
2005-03-22 00:00:00DENIED:
 1.AIR SIZING SUMMARY (MANUAL J) FOR
 AHU'S 1 & 8 INDICATE 5.1 TON UNIT AND
 THE EQUIPMENT SCHEDULE ON PLAN SHEET
 M6.1 INDICATE 3 TON UNIT FOR AHU 1 & 8.
  
 2.PLEASE NOTE, MANUAL J CALCULATIONS
 ARE MISSING FOR AHU 7 & 9.
  
 3.PLAN SHEET M2.1, PLEASE CLARIFY
 OUTSIDE AIR TO AHU'S 1, 3, 4, 5, 6, & 8.
 IT APPEARS THAT ONLY UNITS 7, 2, & 9
 HAVE OUTSIDE AIR.
  
 4.PLAN INDICATES RETURN AIR JUMPER
 FROM THE KITCHEN AREA.PLEASE NOTE PER
 2001 FBC(M) 403.2.2, AIR MAY BE
 TRANSFERRED TO KITCHEN AIR FOR THE
 PURPOSE OF MAKE-UP AIR. AIR FROM THE
 KITCHEN AIR SHALL NOT BE RECIRCULATED.
  
 5.DUCT SMOKE DETECTORS REQUIRED FOR
 SYSTEMS WITH THE AGGREGATE CAPACITY IS
 GREATER THAN 2,000 CFM.
  
 6.FAN SHUTDOW BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS PER 2001
 FBC(M) 606.4.1 EXCEPTION #2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.