Plan Review Notes
Plan Review Notes For Permit 05020338
Permit Number 05020338
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2005-06-02 00:00:00****DENIED****
  
 1) PLEASE NOTE THAT YOUR RESPONSE TO
 COMMENT #1 ILLUSTRATES THE DIFFERENT
 TYPES OF INTERIOR FINISH
 CLASSIFICATIONS. PLEASE REFERENCE THE
 CLASSIFICATION THAT IS SPECIFIC IN
 REGARDS TO THIS PROJECT.
  
 2) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS WHERE
 PROVIDED, SHALL BE WIRED TO THE FIRE
 ALARM SYSTEM TO CAUSE A GENERAL FIRE
 ALARM CONDITION AND NOT SUPERVISORY
 SIGNAL.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE SPRINKLER AND
 FIRE ALARM SYSTEMS.
  
 4) NEW BUILDINGS ARE REQUIRED TO BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE.
  
 5) IN ADDITION TO ELECTRONIC
 SUPERVISION, A CHAIN AND LOCK MUST BE
 PROVIDED FOR THE DOUBLE CHECK DETECTOR
 ASSEMBLY.
  
 6) APPROVED PANIC HARDWARE SHALL BE
 INSTALLED ON DOORS SERVING AN OCCUPANT
 LOAD OF 100 OR MORE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722