| Plan Review Notes For Permit 05020338 |
| Permit Number |
05020338 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-06-02 00:00:00 | ****DENIED**** | | | | | | 1) PLEASE NOTE THAT YOUR RESPONSE TO | | | COMMENT #1 ILLUSTRATES THE DIFFERENT | | | TYPES OF INTERIOR FINISH | | | CLASSIFICATIONS. PLEASE REFERENCE THE | | | CLASSIFICATION THAT IS SPECIFIC IN | | | REGARDS TO THIS PROJECT. | | | | | | 2) IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS, DUCT SMOKE DETECTORS WHERE | | | PROVIDED, SHALL BE WIRED TO THE FIRE | | | ALARM SYSTEM TO CAUSE A GENERAL FIRE | | | ALARM CONDITION AND NOT SUPERVISORY | | | SIGNAL. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR THE FIRE SPRINKLER AND | | | FIRE ALARM SYSTEMS. | | | | | | 4) NEW BUILDINGS ARE REQUIRED TO BE UL | | | CERTIFIED FOR CENTRAL STATION SERVICE. | | | | | | 5) IN ADDITION TO ELECTRONIC | | | SUPERVISION, A CHAIN AND LOCK MUST BE | | | PROVIDED FOR THE DOUBLE CHECK DETECTOR | | | ASSEMBLY. | | | | | | 6) APPROVED PANIC HARDWARE SHALL BE | | | INSTALLED ON DOORS SERVING AN OCCUPANT | | | LOAD OF 100 OR MORE. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2951 OR 805-6722 |
|