| 2005-02-23 00:00:00 | ************ UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE LOAD CALCULATIONS |
| | SUBMITTED ARE FOR A SFR? |
| | PLEASE SHOW LOAD CALCULATIONS FOR A |
| | COMMERCIAL BLDG.P |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | |
| | 2)NOTE: PLEASE SEE 250.6,250.24, |
| | EQUIPMENT GRNDS ARE NOT INSTALLED BEFORE |
| | FIRST MEANS OF DISCONNECT. |
| | |
| | 3)NOTE: PLEASE SEE 310.16 FOR RATING OF |
| | FEEDERS FROM 400A DISC TO PANEL PB-1, |
| | SHOWN AS 350 MCM? ON 400A FUSES. |
| | |
| | 4)NOTE: PLEASE PROVIDE LIGHTING / |
| | RECEPTS FOR AHU'SPER 210.70, 210.63 |
| | |
| | 5)NOTE: PLEASE SEE 210.8(B)(3) IN THE |
| | 2002 NEC. THIS REQUIRES ALL 15- AND |
| | 20-AMPERE, 125-VOLT RECEPTACLES IN |
| | NONDWELLING-TYPE KITCHENS TO BE GFCI |
| | PROTECTED. THIS REQUIREMENT APPLIES TO |
| | EACH AND EVERY 15- AND 20-AMPERE, |
| | 125-VOLT KITCHEN RECEPTACLE, WHETHER OR |
| | NOT THE RECEPTACLE SERVES COUNTERTOP |
| | APPLIANCES. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT ONLY NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |