Plan Review Notes
Plan Review Notes For Permit 05020338
Permit Number 05020338
Review Stop E
Sequence Number 1
Notes
Date Text
2005-02-23 00:00:00************ UNSAT *********
  
 1)NOTE: PLEASE SEE LOAD CALCULATIONS
 SUBMITTED ARE FOR A SFR?
 PLEASE SHOW LOAD CALCULATIONS FOR A
 COMMERCIAL BLDG.P
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 2)NOTE: PLEASE SEE 250.6,250.24,
 EQUIPMENT GRNDS ARE NOT INSTALLED BEFORE
 FIRST MEANS OF DISCONNECT.
  
 3)NOTE: PLEASE SEE 310.16 FOR RATING OF
 FEEDERS FROM 400A DISC TO PANEL PB-1,
 SHOWN AS 350 MCM? ON 400A FUSES.
  
 4)NOTE: PLEASE PROVIDE LIGHTING /
 RECEPTS FOR AHU'SPER 210.70, 210.63
  
 5)NOTE: PLEASE SEE 210.8(B)(3) IN THE
 2002 NEC. THIS REQUIRES ALL 15- AND
 20-AMPERE, 125-VOLT RECEPTACLES IN
 NONDWELLING-TYPE KITCHENS TO BE GFCI
 PROTECTED. THIS REQUIREMENT APPLIES TO
 EACH AND EVERY 15- AND 20-AMPERE,
 125-VOLT KITCHEN RECEPTACLE, WHETHER OR
 NOT THE RECEPTACLE SERVES COUNTERTOP
 APPLIANCES.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  