| 2005-04-02 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1) SHT P-2 SANITARY RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN, NOT DOES IT |
| | MEET CODE REQUIREMENTS: |
| | A) WASH MACHINE IS NOT VENTED, AND AS |
| | DRAWN THE TRAP IS UNDER THE SLAB. |
| | SECTION 901.2.1. |
| | B) SHOWER BATH NEXT TO KITCHEN SANT. |
| | RISER DOES NOT REFLECT THE PIPING SHOWN |
| | ON SHT P-1. SEE RED LINE CORRECTIONS TO |
| | REFLECT FLOOR PLAN. SECTION 104.2.1. |
| | C) VENT FOR W/C IN MASTER BATH IS A |
| | HORIZONTAL DRY VENT IF PIPED AS SHOWN. |
| | SECTIONS 905.3 & 905.4 |
| | D) SHOWER IN MASTER BATH SHALL BE TO |
| | THE RIGHT OF THE BRANCH LINE TO REFLECT |
| | THE FLOOR PLAN SHT P-1. SECTION 104.2.1. |
| | E) THE SIZE OF THE DRAINAGE PIPING SHALL |
| | NOT BE REDUCED IN SIZE IN THE DIRECTION |
| | OF FLOW. SECTION 704.2 (SEE PIPE SIZE |
| | DOWNSTREAM OF THE M/B W/C). |
| | (SEE ALL REDLINE COMMENTS, CORRECTIONS, |
| | AND EXAMPLES ON ONE SET OF PLANS) |
| | 2) SHT P-1 PLUMBING NOTES #12, AIR |
| | CHAMBERS ARE NOT APPROVED. DELETE |
| | REFERENCE FROM NOTES. |
| | 3) PLUMBING GENERAL NOTES #1 INDICATE |
| | COMPLIANCE WITH MARTIN COUNTY |
| | AMMENDMENTS. THE PLANS SHALL BE IN |
| | COMPLIANCE WITH CITY OF W.P.B. CORRECT |
| | REFERENCE. |
| | |
| | CORRECT PLANS AND RESUBMIT FOR REVIEW. |
| | |