| 2005-04-12 00:00:00 | BUILDING REVIEW 2ND CHECKLIST: |
| | 1- |
| | BUILDING REVIEW 2ND CHECKLIST: |
| | |
| | 1- EAST ELEVATION EXCEEDS MAXIMUM |
| | PERCENTAGE OF OPENING ALLOWED BY TABLE |
| | 600 FBC 2001 AT GARDEN COURT. TOTAL |
| | OPENING AREA IS 169SF (PLUS/MINUS) NOT |
| | 64SF. |
| | |
| | 2- REVISED SURVEY SHOWING HOUSE LAYOUT |
| | WAS NOT SUBMITTED. |
| | |
| | 3- ARCHITECT'S RESPONSE TO CHECKLIST |
| | DATED 3-04-05 WAS THAT FIREPLACE WAS |
| | DELETED. DRAWINGS STILL SHOW THE |
| | FIREPLACE. CLARIFY AS REQUIRED. |
| | |
| | 4- SPECIFY SIZE OF HOOD ROOF SCREENS |
| | SHOWN ON THE ELEVATIONS. SEC. 104.2.1.2 |
| | CITY AMENDMETNS TO FBC 2001 AND SECTION |
| | 2309.7 FBC 2001. |
| | |
| | 5- CLARIFY SIZE OF FOOTING FOR PRIVACY |
| | WALL AT GARDEN COURT. NOTESON SHEET |
| | S-1 CALL FOR 10"DEEP FOOTING WHILE, |
| | DETAIL CALLS FOR 12" DEEP FOOTING. |
| | CLARIFY AS REQUIRED. |
| | |
| | 6- TRUSS ANCHOR SCHEDULE: A) CLARIFY |
| | WHERE IS CONNECTOR HUSC412 TAKEN FROM?. |
| | UNABLE TO FIND IT IN THE SIMPSON |
| | CATALOGUE. |
| | NOTE: NEED WOOD TO MASONRY CONNECTOR. |
| | |
| | B) UPDATE TRUSS ANCHOR SCHEDULE. SEE |
| | LATESTSIMPSON AND USP CATALOGUES FOR |
| | SIZE AND NUMBER OF FASTENERS TO BE USED. |
| | CATALOGUES WERE REVISED TO COMPLY WITH |
| | SEC. 1609.4.3 FBC 2001. PROVIDE COMPLETE |
| | ENGINEERING CALCULATIONS THAT COMPLY |
| | WITH SEC. 1609.4.3 FBC 2001 FOR TYPE AND |
| | NUMBER OF FASTENERS THAT DIFFER FROM |
| | THOSE TESTED AND PUBLISHED BY THE |
| | MANUFACTURER. |
| | |
| | 7- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: A) ENTRY DOORS. NEED |
| | IMPACT GLAZING. |
| | B) USP USC63 TRUSS CONNECTOR AND ALL |
| | CONNECTORS THAT ARE SPECIFIED ON THE |
| | TRUSS ANCHOR SCHEDULE. |
| | C) SLIDING GLASS DOORS WITH IMPACT |
| | GLAZING. |
| | D) FRENCH DOORS. IMPACT GLAZING. |
| | E) ARCHED WINDOWS AS SHOWN ON PLANS WITH |
| | IMPACT GLASS. |
| | F) WINDOW MULLIONS THAT MEET THE DESIGN |
| | PRESSURES CALCULATED BY THE ARCHITECT. |
| | CLEARLY MARK ON PRODUCT APPROVAL |
| | SPECIFIC MULLION SIZE AND FASTENERS TO |
| | BE USED TO VERIFY DESIGN PRESSURES. |
| | G) CASEMENT WINDOWS AS SHOWN ON REAR |
| | ELEVATION. |
| | |
| | 8- FLOOR PLAN AND NOTES ON REAR |
| | ELEVATION CALL FOR SINGLE HUNG WINDOWS. |
| | EXTERIOR REAR ELEVATION SHOWS CASEMENT |
| | WINDOW WITH FIXED WINDOW IN THE MIDDLE. |
| | CLARIFY/REVISE AS REQUIRED. |
| | |
| | 9-DETAIL FRAMING FOR ARCHED WINDOWS |
| | CALLS FOR 2X4'S @ 24" O.C. CLARIFY HOW |
| | IS WINDOW ATTACHED. SEE WINDOW PRODUCT |
| | APPROVAL. SEC. 104.2.1.2 CITY AMENDMENTS |
| | TO FBC 2001. |
| | |
| | 10- NEED RECORDED NOTICE OF |
| | COMMENCEMENT. |
| | |
| | 11- OWES $3552.55. PERMIT APPLICANT |
| | DIDN'T PAY FOR THE PERMIT AT TIME OF |
| | APPLICATION. |
| | ADDITIONAL FEES WILL BE CHARGED FOR |
| | RE-SUBMITTAL FEES AFTER 1ST RE-SUB. |
| | |