| Plan Review Notes For Permit 05020322 |
| Permit Number |
05020322 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-17 00:00:00 | DENIED; | | | 1.LINE DRAWING ON P-1 DOESNOT MATCH | | | RISER DIAGRAM ON P-2. | | | 2.BATH # 2 TUB IS NOT VENTED. | | | 3.UTIL. SINK REQUIRES A VENT AND WASHER | | | AND UTIL. SINK ARE IN DIFFERENT PLACES | | | ON RISER DIAGRAM. | | | 4.MASTER BATH. NO BIDET ON FLAT DRAWING | | | OR FLOOR PLAN. SHOWER DRAIN NOT SHOWN ON | | | FLAT DRAWING AND FLAT DRAWING IS NOT | | | LAID OUT THE SAME AS RISER DIAGRAM. | | | PLUMBING PLAN REVIEW; | | | JOHN LEECH | | | 805-6695 |
|