| Notes |
| Date |
Text |
| 2005-02-18 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | | | | 1} THE WHIRLPOOL MUST BE GFI PROTECTED | | | PER 680.43(A)(3)NEC. | | | | | | 2} THE WHIRLPOOL IS NOT LISTED ON THE | | | PANEL SCHEDULE. | | | | | | 3} RECEPTACLES NEED TO BE ADDED TO THE | | | KITCHEN COUNTERTOP TO COMPLY WITH | | | SPACING REQUIREMENTS OF 210.52(C)(1). | | | | | | 4} THE DISCONNECT FOR CU#2 DOES NOT | | | APPEAR TO HAVE CLEARANCE PER 110.26. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|