| Date |
Text |
| 2005-03-04 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- EAST ELEVATION EXCEEDS MAXIMUM |
| | PERCENTAGE OF OPENING ALLOWED BY TABLE |
| | 600 FBC 2001 AT GARDEN COURT. |
| | |
| | 2- PROVIDE DESIGN SPECS FOR 30PSF ATTIC |
| | LIVE LOAD AS REQUIRED BY TABLE 1604.1 |
| | FBC 2001. |
| | |
| | 3- LAYOUT SHOWN ON SURVEY DOESN'T MATCH |
| | PLANS. REVISE AS REQUIRED. |
| | |
| | 4- AN EGRESS EASEMENT (3'-0" MIN.) NEED |
| | TO BE RECORDED IN THE COUNTY RECORDS |
| | WHENUSING ADJOINING LOT FOR EGRESS AS |
| | REQUIRED BY THE BUILDING OFFICIAL. |
| | |
| | 5- PROVIDE COMPLETE SPECS/DETAILS FOR |
| | CEILING INSTALLATION AT ENTRY AND REAR |
| | PORCHES. SPECIFY FASTENER TYPE AND |
| | SPACING AS REQUIRED BY ASTM C-926 AND |
| | ASTM C-1063. SEC. 2504.2 FBC 2001. |
| | |
| | 6- PROVIDE COMPLETE BATHROOM (POWDER |
| | ROOM IS NOT A COMPLETE BATHROOM) WITH |
| | DOOR THAT ALLOWS 29" MIN. CLEAR OPENING |
| | AS REQ'D BY SEC. 11-11 FBC 2001. |
| | |
| | 7- PROVIDE FIREPLACE UL LISTING AND |
| | COMPLETE SPECS AS REQUIRED BY SECTION |
| | 2806 FBC 2001. |
| | |
| | 8- PROVIDE KNEE WALL SECTION/DETAIL AT |
| | ENTRY PORCH SPECIFYING ALL FASTENERS. |
| | SECTION 104.2.1.2 CITY AMENDMENTS TO FBC |
| | |
| | |
| | 9- SPECIFY SIZE OF CONTINUOUS |
| | VENTILATION AT ATTIC AREA AND HOOD ROOF |
| | SCREEN. SEC. 2309.7 FBC 2001. |
| | |
| | 10- PRIVACY WALL FOOTING AT GARDEN COURT |
| | IS ENCROACHING INTO ADJACENT PROPERTY. |
| | REVISE AS REQUIRED. |
| | |
| | 11- CLARIFY SIZE OF INTERIOR BEARING |
| | WALL. 2X4'S OR 2X6'S? SEE SHEET S-2. |
| | |
| | 12- SPECIFY CONNECTORS AT THE ENDS OF |
| | ENTRY PORCH BEAM. SECTION 104.2.1.2 OF |
| | CITY AMENDMENTS TO FBC 2001. |
| | |
| | 13- CLARIFY WHICH METHOD OF GLASS |
| | PROTECTION IS GOING TO BE USED: SHUTTERS |
| | OR MISSILE IMPACT GLAZING ON DOORS AND |
| | WINDOWS. BOTH WERE SUBMITTED. |
| | **PROVIDE COMPLETE INFORMATION FOR |
| | EITHER OPTION WITH LEGIBLE DRAWINGS. |
| | |
| | 14- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: |
| | A) "INSWING" ENTRY DOORS. SEE PLANS. |
| | B) USP USC63 TRUSS CONNECTOR. |
| | C) SLIDING GLASS DOORS (DWGS SUBMITTED |
| | WITH FLORIDA PRODUCT APPROVAL ARE FOR |
| | FRENCH DOORS). |
| | D) SAME DRAWINGS FOR THERMA-TRU DOORS |
| | THAT WERE SUBMITTED FOR FLORIDA PRODUCT |
| | APPROVAL. |
| | E) SMALL AND LARGE GARAGE DOORS WITH |
| | LEGIBLE DRAWINGS. |
| | F) WINDOW MULLIONS.(DRAWINGS SUBMITTED |
| | ARE FOR SLIDING GLASS DOORS). |
| | |
| | 15- BBQ GRILL SPECIFICATIONS DOESN'T |
| | ALLOW TO BUILD GRILL UNDER UNPROTECTED |
| | COMBUSTIBLE CONSTRUCTION AND UNIT IS FOR |
| | OUTDOOR USE ONLY. PROVIDE MANUFACTURER'S |
| | |
| | SPECS THAT ALLOW INSTALLATION OF GRILL |
| | IN THE PORCH. |
| | |
| | 16- REVISE GENERAL NOTES ON SHEET A-1. |
| | STUCCO ON METHAL LATH TO BE 7/8" MIN. AS |
| | REQUIRED BY ASTM C-926. |
| | SAFETY GLASS TO COMPLY WITH ANZI Z97.1, |
| | NOT ABS1-Z97.1. |
| | |
| | 17- TYPICAL EXTERIOR WALL SEC. HAS 2 |
| | DIFFERENT SPECS FOR ROOF SHEATHING |
| | NAILING. CLARIFY SPACING OF NAILS. SEE |
| | COMMENTS AND TABLE 2306.1 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 18- CONNECTOR #3 SPECIFIED ON ROOF |
| | FRAMING PLAN DOESN'T RESIST THE 2717# |
| | UPLIFT LOAD CALCULATED BY THE ENTRY |
| | PORCH GIRDER TRUSS. REVISE AS REQ'D. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 19- PROVIDE COMPLETE DETAIL FOR FRAMING |
| | OF ARCHED OPENINGS TO RECEIVE WINDOWS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 20- TYPICAL CMU PIER DETAIL: SPECIFY |
| | SIZE OF FOOTING AND EMBEDMENT BELOW |
| | GRADE. SPECIFY PIER HEIGHT. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 21- PLEASE PROVIDE ONLY THE DETAILS THAT |
| | APPLY TO THIS PROJECT TO EXPEDITE REVIEW |
| | PROCESS AND AVOID CONFLICTS. |
| | |
| | 22- NEED RECORDED NOTICE OF COMMENCEMENT |
| | |
| | 23- OWES $3552.55 FOR PERMIT. PERMIT |
| | FEES WERE NOT PAID AT TIME OF |
| | APPLICATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |