Plan Review Notes
Plan Review Notes For Permit 05020310
Permit Number 05020310
Review Stop E
Sequence Number 1
Notes
Date Text
2005-02-09 00:00:00 
 PLEASE NOTE PER 104.2.1 PLANS ARE
 REQUIRED TO CONTAIN PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN.
  
 THE AIC RATING PER 110.9 NEC IS REQUIRED
 TO BE ON THE PLAN, PLEASE PROVIDE SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026