| Plan Review Notes For Permit 05020282 |
| Permit Number |
05020282 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | | | | 1) SHT M2 INDICATE DISPOSAL METHOD FOR | | | THE OIL SEPARATED IN THE OIL/WATER | | | SEPARATOR. SECTION 104.2.1. | | | 2) DRAIN LINE FROM COMPRESSED AIR SYSTEM | | | SHALL BE PIPED TO THE EXISTING SANT. | | | DRAIN. MINIMUM SIZE FOR PIPING SHALL BE | | | 2" PIPE. SECTIONS S01.3 & 710.3. A HUB | | | DRAIN IS RECOMMENDED TO KEEP STORM WATER | | | FROM ENTERING THE SANT. SYSTEM. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|