Plan Review Notes
Plan Review Notes For Permit 05020282
Permit Number 05020282
Review Stop P
Sequence Number 1
Notes
Date Text
2005-03-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
  
 1) SHT M2 INDICATE DISPOSAL METHOD FOR
 THE OIL SEPARATED IN THE OIL/WATER
 SEPARATOR. SECTION 104.2.1.
 2) DRAIN LINE FROM COMPRESSED AIR SYSTEM
 SHALL BE PIPED TO THE EXISTING SANT.
 DRAIN. MINIMUM SIZE FOR PIPING SHALL BE
 2" PIPE. SECTIONS S01.3 & 710.3. A HUB
 DRAIN IS RECOMMENDED TO KEEP STORM WATER
 FROM ENTERING THE SANT. SYSTEM.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]