Plan Review Notes
Plan Review Notes For Permit 05020282
Permit Number 05020282
Review Stop M
Sequence Number 1
Notes
Date Text
2005-02-22 00:00:00DENIED:
 PERMIT APPLICATION INDICATES MECHANICAL
 AND ELECTRICAL NOT INCLUDED IN THE VALUE
 OF THE PERMIT.PLANS SUBMITTED ARE FOR
 MECHANICAL AND ELECTRICAL REVIEW.
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION:
  
 1.INDICATE OCCUPANCY TYPE.
  
 2.PROVIDE INFORMATION AS THE USE OF
 THE COMPRESSED AIR.
  
 3.WILL ANY CHEMICALS BE USED FOR THIS
 PROCESS OR STORED AT THIS LOCATION?
  
 4.PROVIDE OUTSIDE AIR CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC(M)TABLE 403.3.
  
 5.INDICATE IF THE RTU'S WILL BE NEW OR
 EXISTING.PROVIDE EQUIPMENT SCHEDULE
 FOR ALL NEW EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.