| Plan Review Notes For Permit 05020280 |
| Permit Number |
05020280 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-09 00:00:00 | PROVISO: | | | TRANSFER GRILLES SHALL BE A MINIMUM OF | | | 50 SQ INCHES PER 100 CFM OF SUPPLY AIR | | | INTO THAT SPACE (2001 FBC(M)601.4 | | | EXCEPTION #2).PLEASE SIZE TRANSFER | | | GRILLES ACCORDINGLY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT(561)805-6719. |
|