| Plan Review Notes For Permit 05020251 |
| Permit Number |
05020251 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-04-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHEETS A, M/E. & E ARE NOT SEALED | | | AND/OR SIGNED, SEALED OR DATED AS | | | REQUIRED BY FAC 61G15-23.002(1) & FS | | | 471.025. | | | 2) FROM PREVIOUS REVIEW: SUBMIT THE | | | FOLLOWING INFORMATION ON THE PLANS TO | | | SHOW COMPLIANCE WITH: | | | C) FLUSH CONTROLS 11-4.16.5 (SHOWN ON | | | THE WRONG SIDE OF THE TANK). | | | F) EXPOSED PIPES & SURFACES 11-4.19.6 | | | G) FAUCETS 11-4.19.7 | | | 3) FROM PREVIOUS REVIEW: | | | TOILET ROOM ADJACENT TO OFFICE SHALL BE | | | ADAPTABLE. SUBMIT A DETAIL SHOWING THE | | | 5' TURNING ARE, AND INDICATE THE W/C TO | | | BE 18" FROM THE CENRTERLINE OF THE | | | FIXTURE TO THE WALL. | | | ***NEW COMMENT*** | | | 1B) SHOW CLEAR FLOOR SPACE FOR WATER | | | COOLER PER SECTION 11-4.15.5. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|