Plan Review Notes
Plan Review Notes For Permit 05020251
Permit Number 05020251
Review Stop E
Sequence Number 2
Notes
Date Text
2005-04-18 00:00:00**** UNSAT *****
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SOME ELECTRICAL ITEMS ON
 PLANS STILL DO NOT CONTAIN CIRCUITING.
  
 2)NOTE: PLEASE CORRELATE CIRCUITS ON
 PLANS WITH PANEL SCHEDULE, PLEASE SEE
 EXT LT CIRCUIT.
  
 3)NOTE: PLEASE SEE NO SEC'S ARE SHOWN ON
 RISER.
 PLEASE SEE 310.16,240.4.
  
 4)NOTE: PLEASE SEE LOCATION OF METER AND
 MAIN DOES NOT MEET 110.26. NEW HAND RAIL
 MAY NOT BE PLACE IN FRONT OF EQUIPMENT
 AS SHOWN ON PLANS.
  
 5)NOTE: PLEASE SEE LOAD CALCAULTIONS
 NEED TO BE SHOWN PER NEC 220
 PLEASE SEE 220.3B4 ALSO.
  
 6)NOTE: PLEASE SEE MISSING SIGN CIRCUIT
 PER 600.5
  
 7)NOTE: PLEASE CLARIFY LOAD, OCP AND AWG
 FOR AHU?
 PLEASE SEE 13.2 AMPS, W/ 50A OCP
  
 8)NOTE: PLEASE SEE PLANS ARE NOT SIGNED,
 DATED OR SEALED BY ENGINEER OF RECORD ON
 TITLE BLOCK.
 FS 471.025
 PLEASE ALSO SEE BLDG REVIEW COMMENTS
 PERTAINING TO ENGINEER'S LICENSE NOT
 BEING CURRENT ON STATE WEBSITE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  