Plan Review Notes
Plan Review Notes For Permit 05020251
Permit Number 05020251
Review Stop P
Sequence Number 1
Notes
Date Text
2005-03-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SUBMIT A DETAIL FOR THE ACCESSIBLE
 TOILET ROOM SHOWING COMPLIANCE WITH:
 A) HEIGHT 11-4.16.3
 B) GRAB BARS 11-4.16.4
 C) FLUSH CONTROLS 11-4.16.5
 D) DISPENSERS 11-4.16.6
 E) HEIGHT & CLEARANCES 11-4.19.2
 F) EXPOSED PIPES & SURFACES 11-4.19.6
 G) FAUCETS 11-4.19.7
 H) THE W/C SHALL BE 18" FROM THE
 CENTERLINE OF THE FIXTURE TO THE WALL.
 FIGURE 28.
 2) TOILET ROOM ADJACENT TO OFFICE SHALL
 BE ACCESSIBLE. SUBMIT A DETAIL SHOWING
 THE BACKING FOR THE GRAB BARS, THE 5'
 TURNING AREA, & INDICATE THE W/C TO BE
 18" FROM THE CENTERLINE OF THE FIXTURE
 TO THE WALL.
 3) IN THE REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. SECTION 704.5 - THE DEMO'D
 PIPE SHALL BE INSPECTED PRIOR TO
 COVERING.
 4) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. ALSO SEE SECTION 410.1.
 5) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE OF THE BUILDING. SECTION
 608.13.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]