| Plan Review Notes For Permit 05020251 |
| Permit Number |
05020251 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-03 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SUBMIT A DETAIL FOR THE ACCESSIBLE | | | TOILET ROOM SHOWING COMPLIANCE WITH: | | | A) HEIGHT 11-4.16.3 | | | B) GRAB BARS 11-4.16.4 | | | C) FLUSH CONTROLS 11-4.16.5 | | | D) DISPENSERS 11-4.16.6 | | | E) HEIGHT & CLEARANCES 11-4.19.2 | | | F) EXPOSED PIPES & SURFACES 11-4.19.6 | | | G) FAUCETS 11-4.19.7 | | | H) THE W/C SHALL BE 18" FROM THE | | | CENTERLINE OF THE FIXTURE TO THE WALL. | | | FIGURE 28. | | | 2) TOILET ROOM ADJACENT TO OFFICE SHALL | | | BE ACCESSIBLE. SUBMIT A DETAIL SHOWING | | | THE BACKING FOR THE GRAB BARS, THE 5' | | | TURNING AREA, & INDICATE THE W/C TO BE | | | 18" FROM THE CENTERLINE OF THE FIXTURE | | | TO THE WALL. | | | 3) IN THE REMOVAL OF ANY PART OF A | | | DRAINAGE SYSTEM, DEAD ENDS SHALL BE | | | PROHIBITED. SECTION 704.5 - THE DEMO'D | | | PIPE SHALL BE INSPECTED PRIOR TO | | | COVERING. | | | 4) A DRINKING FOUNTAIN IS REQUIRED PER | | | TABLE 403.1. ALSO SEE SECTION 410.1. | | | 5) AN RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE OF THE BUILDING. SECTION | | | 608.13.2. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|