Plan Review Notes
Plan Review Notes For Permit 05020251
Permit Number 05020251
Review Stop M
Sequence Number 1
Notes
Date Text
2005-03-04 00:00:00DENIED:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) TABLE
 403.3.
  
 2.PLEASE PROVIDE EXISTING EQUIPMENT
 INFORMATION (I.E., MANUFACTURER, MODEL
 NUMBER, ETC.).PLEASE NOTE, UNITS THAT
 HAVE THE DESIGN CAPACITY GREATER THAN
 2,000 CFM SHALL HAVE FAN SHUTDOWN BY
 DUCT SMOKE DETECTOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.