2005-02-23 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SUBMIT MIN ELECTRICAL
 REQUIRED UNDER 2002 NEC FOR NEW OFFICE
 SPACE.
 PLEASE SHOW ALL NEW/ EXISTING ELECTRICAL
 ON PLANS.
 PLEASE INCLUDE ALL CIRCUITING ON PLANS
 AND CORRELATE WITH A PANEL SCHEDULE TO
 BE SUBMITTED.
 PLEASE INCLUDE LOAD CALCULATIONS FOR NEW
 AND EXISTING, INDICATE SIZE OF EXISTING
 OR NEW SERVICE. IF NEW, PLEASE SUBMIT
 RISER DIAGRAM WITH ALL INFORMATION AS
 REQUIRED.
 310.16,240.4,225.31,250.50,110.9 ETC
 215.5
 PLEASE SEE 700.12E FOR CIRCUITING OF EM/
 EXT LTS.
 PLEASE SHOW ALL MIN REQUIRED EGRESS
 LIGHTING PER LS 101 5-8.
  
  
 2 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  