Plan Review Notes
Plan Review Notes For Permit 05020251
Permit Number 05020251
Review Stop B
Sequence Number 1
Notes
Date Text
2005-02-15 00:00:00PERMIT #05020251
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1. IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025 FOR MORE
 INFORMATION.
  
 2. SEE FBC3401.2.2.2, CHANGE OF
 OCCUPANCY.
  
 3. THE ACCESSIBLE PARKING SPACE IS TO
 COMPLY WITH CITY OF WEST PALM BEACH
 STANDARDS, SEE ATTACHED.
  
 4. SHOW THE ACCESSIBLE ROUTE IN
 COMPLIANCE WITH FBC11-4.3.2, INCLUDING
 SLOPE AND WIDTH.
  
 5. TWO AUTO SLIDING GATES ARE SHOWN ON
 THE PLAN.SEPARATE PERMITS REQUIRED.
 PLEASE NOTE THAT THERE AREN?T ANY
 DETAILS FOR THE GATES AND THEY ARE NOT
 SHOWN ON THE ELECTRIC PLAN.
  
 6. THE ?HANDICAP RAMP? IN THE REAR OF
 THE BUILDING SHOWS THE RAILING ANCHORED
 TO THE WALL AT A WINDOW.CLARIFY; IF
 NECESSARY, PROVIDE AN ELEVATION.
  
 7. THE ACCESSIBLE RAMP IS TO HAVE
 LANDINGS, SEE 11-4.8.4.
  
 8. THE RAMP IS TO BE IN COMPLIANCE WITH
 FBC11-4.8.1 THROUGH 11-4.8.8, SHOW
 COMPLIANCE WITH ALL REQUIREMENTS ON THE
 PLAN.
  
 9. SHOW MANEUVERING CLEARANCE FOR THE
 DOORS AT THE RECEPTION/WAITING ROOM,
 OFFICE #4, AND THE ACCESSIBLE BATHROOM,
 FBC CHAPTER 11 FIGURE 25.
  
 10. THE BATHROOM AT OFFICE #4 IS TO
 COMPLY WITH FBC11-4.1.3(11) (ADAPTABLE).
 PROVIDE A DETAIL.
  
 11. PROVIDE DETAILS FOR THE ACCESSIBLE
 BATHROOM SINK, WC, GRAB BARS.NO
 DIMENSIONS OR ELEVATIONS ARE SHOWN ON
 THE PLAN.
  
 12. THE TYPICAL CONCRETE STAIR SHOWS AN
 8IN RISER AND A 16IN TREAD.THE STAIRS
 ARE TO COMPLY WITH FBC1007.3.1 AND
 1007.3.2.THE STAIRS ARE NOT SHOWN ON
 THE FLOOR PLAN.
  
 13. PROVIDE ALL DIMENSIONS FOR THE
 STAIR, INCLUDING TOTAL HEIGHT, WIDTH.
  
 14. HANDRAILS REQUIRED FOR THE STAIRS IN
 COMPLIANCE WITH FBC1007.5.
  
 15. SHOW HEIGHT OF STAIRS; OVER 30IN
 REQUIRES GUARDRAILS IN COMPLIANCE WITH
 FBC1015.
  
 16. THE DETAIL FOR THE HANDICAP RAILING
 DOES NOT PROVIDE A HEIGHT.SPECIFY
 DESIGN CRITERIA IN COMPLIANCE WITH
 FBC1608.2.2.THE RAILING DETAIL, WHICH
 SHOWS TWO FREESTANDING RAILS, CONFLICTS
 WITH THE PROPOSED PLAN, WHICH SHOWS ONE
 RAILING ANCHORED TO THE WALL.
  
 17. ARE THE OFFICES FOR ONE TENANT OR
 MULTIPLE TENANTS?NOTE ON THE PLAN.
  
 18. PROVIDE THE DIMENSION FROM THE
 PROPERTY LINE AND AN ELEVATION, WITH
 DIMENSIONS, FOR THE NORTH SIDE OF THE
 BUILDING TO DETERMINE FBC TABLE 600
 COMPLIANCE.
  
 19. PROVIDE DIMENSIONS FOR THE EXTERIOR
 DOORS.