| 2005-02-15 00:00:00 | PERMIT #05020251 |
| | |
| | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1. IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.561-233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 2. SEE FBC3401.2.2.2, CHANGE OF |
| | OCCUPANCY. |
| | |
| | 3. THE ACCESSIBLE PARKING SPACE IS TO |
| | COMPLY WITH CITY OF WEST PALM BEACH |
| | STANDARDS, SEE ATTACHED. |
| | |
| | 4. SHOW THE ACCESSIBLE ROUTE IN |
| | COMPLIANCE WITH FBC11-4.3.2, INCLUDING |
| | SLOPE AND WIDTH. |
| | |
| | 5. TWO AUTO SLIDING GATES ARE SHOWN ON |
| | THE PLAN.SEPARATE PERMITS REQUIRED. |
| | PLEASE NOTE THAT THERE AREN?T ANY |
| | DETAILS FOR THE GATES AND THEY ARE NOT |
| | SHOWN ON THE ELECTRIC PLAN. |
| | |
| | 6. THE ?HANDICAP RAMP? IN THE REAR OF |
| | THE BUILDING SHOWS THE RAILING ANCHORED |
| | TO THE WALL AT A WINDOW.CLARIFY; IF |
| | NECESSARY, PROVIDE AN ELEVATION. |
| | |
| | 7. THE ACCESSIBLE RAMP IS TO HAVE |
| | LANDINGS, SEE 11-4.8.4. |
| | |
| | 8. THE RAMP IS TO BE IN COMPLIANCE WITH |
| | FBC11-4.8.1 THROUGH 11-4.8.8, SHOW |
| | COMPLIANCE WITH ALL REQUIREMENTS ON THE |
| | PLAN. |
| | |
| | 9. SHOW MANEUVERING CLEARANCE FOR THE |
| | DOORS AT THE RECEPTION/WAITING ROOM, |
| | OFFICE #4, AND THE ACCESSIBLE BATHROOM, |
| | FBC CHAPTER 11 FIGURE 25. |
| | |
| | 10. THE BATHROOM AT OFFICE #4 IS TO |
| | COMPLY WITH FBC11-4.1.3(11) (ADAPTABLE). |
| | PROVIDE A DETAIL. |
| | |
| | 11. PROVIDE DETAILS FOR THE ACCESSIBLE |
| | BATHROOM SINK, WC, GRAB BARS.NO |
| | DIMENSIONS OR ELEVATIONS ARE SHOWN ON |
| | THE PLAN. |
| | |
| | 12. THE TYPICAL CONCRETE STAIR SHOWS AN |
| | 8IN RISER AND A 16IN TREAD.THE STAIRS |
| | ARE TO COMPLY WITH FBC1007.3.1 AND |
| | 1007.3.2.THE STAIRS ARE NOT SHOWN ON |
| | THE FLOOR PLAN. |
| | |
| | 13. PROVIDE ALL DIMENSIONS FOR THE |
| | STAIR, INCLUDING TOTAL HEIGHT, WIDTH. |
| | |
| | 14. HANDRAILS REQUIRED FOR THE STAIRS IN |
| | COMPLIANCE WITH FBC1007.5. |
| | |
| | 15. SHOW HEIGHT OF STAIRS; OVER 30IN |
| | REQUIRES GUARDRAILS IN COMPLIANCE WITH |
| | FBC1015. |
| | |
| | 16. THE DETAIL FOR THE HANDICAP RAILING |
| | DOES NOT PROVIDE A HEIGHT.SPECIFY |
| | DESIGN CRITERIA IN COMPLIANCE WITH |
| | FBC1608.2.2.THE RAILING DETAIL, WHICH |
| | SHOWS TWO FREESTANDING RAILS, CONFLICTS |
| | WITH THE PROPOSED PLAN, WHICH SHOWS ONE |
| | RAILING ANCHORED TO THE WALL. |
| | |
| | 17. ARE THE OFFICES FOR ONE TENANT OR |
| | MULTIPLE TENANTS?NOTE ON THE PLAN. |
| | |
| | 18. PROVIDE THE DIMENSION FROM THE |
| | PROPERTY LINE AND AN ELEVATION, WITH |
| | DIMENSIONS, FOR THE NORTH SIDE OF THE |
| | BUILDING TO DETERMINE FBC TABLE 600 |
| | COMPLIANCE. |
| | |
| | 19. PROVIDE DIMENSIONS FOR THE EXTERIOR |
| | DOORS. |