| Date |
Text |
| 2006-02-10 00:00:00 | ************ UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE PLANS DO NOT INDICATE |
| | OR SHOW GROUPING OF MAINS? ALTHOUGH ONLY |
| | ONE MAIN IS SHOWN. |
| | PLEASE VERIFY WHY SITE PLANS SHOWS MAINS |
| | INT TWO DIFFERENT LOCATIONS.? |
| | MAINS MUST BE GROUPED IN CLOSE |
| | PROXIMITY, WHICH THAT DOES APPEAR TO BE |
| | THE CASE AS SHOWN ON PLANS. |
| | 230.72 |
| | |
| | 2)NOTE: PLEASE CORRELATE NOTES ON RISER |
| | DIAGRAM AS THIS SHOWS TWO DIFFERENT |
| | SIZES SERVICES.?600A , 800A? |
| | PLEASE SEE PANELS 120/208V. |
| | PLEASE SHOW LOAD CALCULATIONS AND |
| | VOLTAGE FIGURED AS TOTAL DEMAND DOES NOT |
| | SEEM TO CORRELATE WITH A 120/208V |
| | 3-PHASE SYSTEM OR 277/480V? |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | SYSTEM. PLEASE SEE THE "EQUIPMENT |
| | GROUNDING CONDUCTORS" AND THE NEUTRAL IS |
| | "ONLY" BONDED AT THE FIRST MEANS OF |
| | DISCONNECT. PLEASE SEE DETAIL AS THIS |
| | SHOWS THE PARALLELING OF THE NEUTRAL AND |
| | OBJECTIONABLE CURRENTS PER 250.6 |
| | PLEASE PROVIDE A ONE-LINE OF THE |
| | GROUNDING ELECTRODE SYSTEM ON RISER |
| | DIAGRAM. 250.58 |
| | |
| | 4)NOTE: PLEASE SEE ONLY3-PHASE PANELS |
| | ARE BEING SHOWN, HOWEVER, PLEASE SEE |
| | RISER INDICATES SINGLE PHASE AND THREE |
| | PHASE FEEDERS??? |
| | PLEASE ALSO SEE TYPICAL DETAIL WHICH |
| | SHOWS BOTH ?? |
| | 215.5 |
| | IF SERVICE IS THREE PHASE ALL THE WAY |
| | THROUGH TO TENANT, PLEASE ADJUST AND |
| | CORRELATE ALL PANELS. |
| | |
| | |
| | *** PLEASECORRELATE ANDCOMPLETE |
| | |
| | PLEASE SUBMIT ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |