| 2005-06-24 00:00:00 | PROVISO: | | | PLAN SHEET M7.01 SPLIT SYSTEM A/C UNIT | | | SCHEDULE, NOTE #7 - ALL A/C UNITS HANG | | | IN WAREHOUSE WITH TOP OF THE UNITS AT 19 | | | FT AFF.PER 2001 FBC(M)306.5, WHERE | | | EQUIPMENT IS INSTALLED AT A HEIGHT | | | GREATER THAN 16 FT, PERMANENT MEANS OF | | | ACCESS IS REQUIRED.THIS HEIGHT WILL | | | EXTEND FROM THE FLOOR LEVEL TO THE LEVEL | | | SERVICE SPACE OF THE EQUIPMENT.PLEASE | | | PROVIDE INFORMATION ON HOW THE EQUIPMENT | | | IS TO BE SERVICED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|