Plan Review Notes
Plan Review Notes For Permit 05020247
Permit Number 05020247
Review Stop P
Sequence Number 1
Notes
Date Text
2005-03-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT L-3 SHOW THE LOCATION OF THE
 CONTROLLER/TIMER, AND RAIN SENSOR.
 SECTION 104.2.1.
 2) SHT C.5 RPZ BACKFLOW IS REQUIRED ON
 THE WATER SERVICE TO EACH BUILDING.
 SECTION 608.13.2.
 3) INDICATE THE SF AREA FOR EACH UNIT TO
 CALCULATED THE MINIMUM FACILITIES PER
 TABLES 1003.1 & 403.1.
 4) SHT A3.06 DETAIL #3 PROVIDE
 CALCULATIONS SHOWING COMPLIANCE WITH
 SECTIONS 11-4.26.3(2)(3)(4).
 CALCULATIONS FROM THE ENGINEER REQD.
 5) SHT A3.09 SHOW COMPLIANCE WITH
 SECTION 11-4.19.4 EXPOSED PIPES &
 SURFACES. EXPOSED PIPES SHALL BE
 INSULATED TO PREVENT INJURY.
 6) SHTS P5.01 & P5.02 WATER RISER
 DIAGRAMS, SECTION 606.1(4) FULL OPEN
 VALVES ARE REQUIRED ON EVERY WATER DOWN
 FEED PIPE. SECTION 606.2(2) SHUT OFF
 VALVES REQUIRED FOR HOSE BIBBS. THESE
 VALVES SHALL BE SHOWN ON ALL ISOMETRIC
 WATER RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]