| Plan Review Notes For Permit 05020246 |
| Permit Number |
05020246 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-02-10 00:00:00 | ************ UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE PLANS WHICH WERE | | | REDLINED ON 11/10/05 FOR GROUPING OF | | | MAINS WHICH DO NOT APPEAR AS SHOWN ON | | | SITE PLANS. | | | MAINS MUST BE GROUPED IN CLOSE | | | PROXIMITY, WHICH THAT DOES APPEAR TO BE | | | THE CASE AS SHOWN ON [PLANS. | | | 230.72 | | | | | | 2)NOTE: PLEASE SEE CORRELATE PLANS, | | | PANEL SCHEDULES, LOAD CALCUALTIONS AND | | | RISER DIAGRAM. | | | PLEASE SEE PANELS 120/208V, SERVICE AS | | | 277/480V AND LOADS AS ???? | | | 215.5 | | | | | | 3)NOTE: PLEASE SEE GROUNDING ELECTRODE | | | SYSTEM WHICH WILL CHANGE. PLEASE SEE | | | PLANS/RISER DOES NOT INDICATE GE SYSTEM. | | | | | | 250.50,250.66 ETC | | | | | | 4)NOTE: PLEASE SEE ONLY3-PHASE PANELS | | | ARE BEING SHOWN, HOWEVER, PLEASE SEE | | | RISER INDICATES SINGLE PHASE AND THREE | | | PHASE FEEDERS???CIRCIRLED NOTES #9 AND | | | #10. | | | PLEASE ALSO SEE TYPICAL DETAIL WHICH | | | SHOWS BOTH ?? | | | 215.5 | | | IF SERVICE IS THREE PHASE ALL THE WAY | | | THROUGH TO TENANT, PLEASE ADJUST AND | | | CORRELATE ALL PANELS | | | | | | | | | *** PLEASE CORRELATE PLANS FOR REVIEW OF | | | CODE COMPLIANCE. | | | | | | PLEASE SUBMIT ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|