| Plan Review Notes For Permit 05020246 |
| Permit Number |
05020246 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-06-17 00:00:00 | PROVISO: | | | PLAN SHEET M7.01 SPLIT SYSTEM A/C UNIT | | | SCHEDULE, NOTE #7 - ALL AC UNITS HANG IN | | | WAREHOUSE WITH TOP OF THE UNITS AT 19 FT | | | AFF.PER 2001 FBC(M)306.5, WHERE | | | EQUIPMENT IS INSTALLED AT A HEIGHT | | | GREATER THAN 16 FT, PERMANENT MEANS OF | | | ACCESS REQUIRED.THIS HEIGHT WILL | | | EXTEND FROM THE FLOOR LEVEL TO THE LEVEL | | | SERVICE SPACE OF THE EQUIPMENT.PLEASE | | | PROVIDE INFORMATION HOW EQUIPMENT IS TO | | | BE SERVICED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|